Portable Power Station Runtime Calculator
Direct answer: estimated run time (hours) = station capacity (Wh) × usable share × inverter efficiency ÷ average load watts. Average load = Σ(running watts × quantity × duty cycle %). Worked fridge example: a 1,024 Wh station at 80% usable (LiFePO4 cycle-life DoD from a cell datasheet) and 90% inverter efficiency has 1,024 × 0.80 × 0.90 = 737.28 Wh of AC energy. A DOE FEMP ENERGY STAR example top-freezer (18.1 ft³) uses 363.5 kWh/yr; average watts = 363.5 × 1,000 ÷ 8,760 ≈ 41.5 W (cycling already folded into the annual figure, so duty = 100%). 737.28 ÷ 41.5 ≈ 17.8 hours (about 17 h 46 min). That is an estimate — real fridges and stations vary. Motor start surge still uses a cited ~3× multiplier on compressor-on watts derived as 41.5 ÷ (1/3) ≈ 124.5 W from the BSE-301 one-third run rule, so start ≈ 374 W. People who rely on medical equipment such as a CPAP should check the device maker's guidance on battery use; run time also varies with humidifier and heater settings. This page is not medical advice.
What to measure
Worked example: Fridge example: DOE FEMP ENERGY STAR 363.5 kWh/yr → 41.5 W avg. 1,024 Wh × 80% × 90% ÷ 41.5 ≈ 17 h 46 min. Estimate only.
How it works
Estimated run time (hours) = capacity (Wh) × (usable % ÷ 100) × (inverter efficiency % ÷ 100) ÷ average load (W). Average load (W) = sum over appliances of (running watts × quantity × duty % ÷ 100). Peak running load = sum of (running watts × quantity). For a DC or USB load the inverter term is 1 (100%). Fridge preset: DOE FEMP Table 1 ENERGY STAR model annual use 363.5 kWh/yr (18.1 ft³ top-freezer, automatic defrost). Average watts = 363.5 × 1,000 ÷ 8,760 ≈ 41.5 W; duty defaults to 100% because the annual figure already includes compressor cycling. Fridge surge: BSE-301 notes motors start at about three times running current. Compressor-on watts ≈ 41.5 ÷ (1/3) ≈ 124.5 W using the same guide's one-third run rule, so start ≈ 3 × 124.5 ≈ 374 W. Sump surge uses Liberty Pumps 250-Series locked-rotor ÷ full-load amps (8 ÷ 5.2 ≈ 1.54×). Sump duty defaults to 5% (~1.2 h/day) as an editable assumption shown on the row — real sump runtime depends heavily on rainfall and water table; it is not a published standard.
More worked examples
- Fridge on a 1,024 Wh station (defaults): usable AC 737.28 Wh ÷ 41.5 W ≈ 17.77 h (17 h 46 min).
- Same fridge on a 2,048 Wh station at 80%/90%: 1,474.56 ÷ 41.5 ≈ 35.53 h (35 h 32 min).
- CPAP at 53 W continuous on 512 Wh, 80% usable, 90% inverter: 368.64 ÷ 53 ≈ 6.96 h (6 h 57 min). Humidifier settings change this.
- Wi-Fi router 5.7 W + LED 11 W + laptop 50 W (all 100% duty) on 256 Wh, 80%/90%: 184.32 ÷ 66.7 ≈ 2.76 h (2 h 46 min).
- Sump pump 598 W at 5% duty (editable assumption) alone on 1,024 Wh, 80%/90%: average 29.9 W → 737.28 ÷ 29.9 ≈ 24.66 h. Storms can raise duty a lot — edit the percentage.
- DC/USB-only loads: 256 Wh pack at 80% usable with inverter 100% and 20 W USB draw → 204.8 ÷ 20 = 10.24 h (10 h 14 min).
- Space heater 1,500 W at 100% duty on 3,600 Wh, 80%/90%: usable AC 2,592 Wh ÷ 1,500 = 1.73 h (1 h 44 min) — heaters drain stations quickly.
- Side-by-side ENERGY STAR about 630 kWh/yr (ENERGY STAR 2024 Quick Reference): 630 × 1,000 ÷ 8,760 ≈ 71.9 W average; on 1,024 Wh at 80%/90% → 737.28 ÷ 71.9 ≈ 10.3 h.
How to measure
- Read the power station label for Wh (or Ah and volts: Wh ≈ Ah × V) and any usable-capacity note.
- Read each appliance nameplate for watts (or amps × volts). A plug-in watt meter shows real running watts and cycling.
- For fridges, prefer the EnergyGuide or ENERGY STAR annual kWh: average W = kWh/yr × 1,000 ÷ 8,760 (duty already included). If you only have compressor running watts, BSE-301's ÷3 rule is a sourced duty starting point.
- Enter the station inverter's continuous and surge watts from its specs if you want the surge warning.
- For CPAP and other medical devices, follow the maker's published battery and power guidance.
Common mistakes
- Using an old table's compressor running watts (hundreds of W) as a continuous 100% load — modern ENERGY STAR annual kWh implies ~40–70 W on average.
- Ignoring inverter losses on AC outlets (or leaving 90% for a pure DC/USB load — use the toggle).
- Treating generic Wh presets as a specific brand's usable capacity.
- Assuming a sump runs only a few minutes a day in every basement — edit duty for wet conditions.
- Skipping motor start: a station that can run a fridge continuously may still fault on compressor start if surge rating is low.
- Relying on this page for medical-device backup planning without checking the device maker.
Assumptions
- Station capacity is the watt-hour (Wh) rating on the label. Presets are generic Wh sizes only (256, 512, 1,024, 2,048, 3,600) — not brand endorsements.
- Usable share defaults to 80%, matching the Lithium Werks 32140 LiFePO4 datasheet cycle-life rating at 80% depth of discharge. Some portable stations allow a higher usable share — edit this field to the usable Wh or DoD on your station's label.
- Inverter efficiency defaults to 90% for AC loads as an editable estimate below the >95% typical grid-tied range in the Sandia CEC inverter protocol (same default as the amp-hours page). The DC/USB toggle sets efficiency to 100%.
- Appliance watts: fridge average from DOE FEMP ENERGY STAR 363.5 kWh/yr (÷ 8,760 h); sump from Liberty Pumps 250-Series FLA; CPAP 53 W typical (ResMed AirSense 10 clinical guide, no brand in UI); router 5.7 W (NRDC); laptop 50 W, TV 120 W and heater 1,500 W from VCE BSE-301 (older DOE Energy Saver table values — dated but as published); LED 11 W (DOE FEMP ENERGY STAR example). Phone-charger presets omitted — no solid DOE/ENERGY STAR wattage table.
- Duty cycle: fridge preset uses 100% because ENERGY STAR/FEMP annual kWh already averages cycling. Sump 5% is a labeled, editable assumption on the appliance row. Always-on loads default to 100%.
- Optional surge and continuous ratings compare estimated motor start watts and peak running watts to numbers you enter from the station label. Exceeding them shows a warning only — not a design check.
- CPAP note: run time varies with humidifier and heated-tube settings. Anyone relying on medical equipment should follow the device maker's battery-use guidance. This page does not give medical advice.
- Results are estimates. Temperature, battery age, inverter behavior, compressor cycling and simultaneous loads all change real hours.
Frequently asked questions
How long will a power station run a fridge?
Using the ENERGY STAR/FEMP average-watts fridge and defaults: 1,024 Wh × 80% × 90% ÷ 41.5 W ≈ 17.8 hours (about 17 h 46 min). Change capacity, usable share, efficiency and your fridge's measured or labeled kWh/yr for a better estimate.
How do you calculate power station run time?
Hours = Wh × usable share × inverter efficiency ÷ average load watts. Average load adds each appliance's watts × quantity × duty cycle.
What is a fridge duty cycle?
Compressors cycle on and off. This page's fridge preset uses average watts from annual ENERGY STAR/FEMP kWh (duty already folded in at 100%). If you enter nameplate running watts instead, BSE-301's divide-by-3 rule (~33% duty) is a sourced starting point for compressor cycling.
How many watts does a refrigerator use?
DOE FEMP's ENERGY STAR example top-freezer (18.1 ft³) is 363.5 kWh/yr → 363.5 × 1,000 ÷ 8,760 ≈ 41.5 W on average. Nameplate running watts when the compressor is on are higher; a plug-in watt meter shows both.
Will a power station start a fridge or sump pump?
Motors draw a short start surge. BSE-301 notes motors start at about three times running current. Enter your station's surge rating to see a warning if the estimated start watts exceed it. This is not a substitute for the maker's specs.
How long will a station run a CPAP?
A typical figure from one manufacturer's clinical guide is 53 W (57 VA) with humidifier. At 1,024 Wh × 80% × 90% ÷ 53 ≈ 13.9 hours. Humidifier and heater settings change draw; follow the device maker's battery guidance. Not medical advice.
What does usable capacity mean?
Some of the rated Wh may be reserved by the battery-management system. This page defaults to 80% usable to match the Lithium Werks LiFePO4 datasheet cycle-life rating at 80% DoD. Edit to your station's stated usable Wh or DoD when listed.
DC or USB loads vs the AC outlet?
Check DC/USB load to set inverter efficiency to 100%. AC outlets go through the inverter (default 90%).
Related calculators
- Amp-hours to kWh battery calculator – for Ah × volts battery math and run time
- Watts, volts and amps calculator – to turn nameplate amps into watts
- kW to kWh calculator – for kW × hours = kWh
- Space heater cost calculator – if you are estimating heater energy cost instead of battery hours
- Generator size calculator (watts) – for running + starting watts when sizing a generator instead
- Electrical & power calculators – Ah, watts, kW, kWh, voltage drop and home heating power tools
Sources
Formulas and reference values are from these sources. Page content last updated 2026-10-28.
- U.S. DOE FEMP Purchasing Energy-Efficient Residential Refrigerators Table 1: ENERGY STAR model annual energy use 363.5 kWh/yr for an 18.1 ft³ top-freezer with automatic defrost (10 CFR 430 Appendix A)
- Virginia Cooperative Extension BSE-301: Estimating appliance and home electronic energy use (Wattage × hours ÷ 1,000 = daily kWh; portable heater 750-1,500 W)
- Sandia National Laboratories PVPMC: CEC Inverter Test Protocol (typical grid-tied inverter efficiencies exceed 95%; CEC weighted efficiency)
- Lithium Werks 32140 Energy Cell datasheet: LiFePO4 nominal cell voltage 3.2 V; cycle life stated at 80% DOD
- Liberty Pumps 250-Series engineering specification: 1/3 hp sump/effluent, 115 V full-load amps 5.2 A, locked-rotor amps 8 A
- ResMed AirSense 10 clinical guide technical specifications: typical power consumption 53 W (57 VA); peak 104 W (108 VA)
- NRDC (EPA-funded) Small Network Equipment Energy Consumption in U.S. Homes (2013): average router power 5.7 W
- U.S. DOE FEMP Purchasing Energy-Efficient Light Bulbs Table 2: 800-lumen LED input power 5.9 to 10.5 W; Table 1 ENERGY STAR model example 11 W
- NIST SP 330 (2019): The International System of Units (watt = J/s, volt = W/A)