Generator Size Calculator (Running and Starting Watts)

Editorial team, built with AI assistance, checked against University of Florida IFAS, Virginia Tech and Oklahoma State Extension motor tables and sizing method, with CPSC, OSHA and Ready.gov safety guidance, updated .

Direct answer: minimum generator watts ≈ total running watts of everything on at once + the largest single extra starting surge (starting − running watts). This is the method in Virginia Tech publication 442-067 (Table 4) and Oklahoma State Extension. Example: fridge 725 W + furnace blower 575 W + sump pump 400 W + 10 LED bulbs 110 W = 1,810 W running; the blower's 2,300 − 575 = 1,725 W surge is the largest, so the minimum is about 3,535 W. These are estimates. Your nameplates govern.

Elevation (optional)

Default 3.5% per 1,000 ft from sea level (Westinghouse WGen20000 and Cummins Onan P4500iDF manuals). The Cummins Onan RV manual's table is rated to 500 ft; Onan bulletin T-017 uses about 4% per 1,000 ft above 1,000 ft. Derating varies by model; check your generator's manual.

What to measure

Add the running wattsBars for a fridge, furnace blower, sump pump and lights add to a total running load of 1,810 watts.725575400110FridgeBlowerSumpLightsTotal running = 725 + 575 + 400 + 110= 1,810 W
Total running W = sum of running watts
Add the largest start surgeThe running total plus the single largest extra starting surge gives the minimum generator watts.1,810 WTotal running+1,725 WLargest start − runMinimum 3,535 W
Minimum W = running total + largest (start − run)
Service and pedestal capacityThree boxes: 30 amp at 120 volt is 3,600 watts, 50 amp at 240 volt is 12,000 watts, 200 amp at 240 volt is 48,000 watts.30 A × 120 V3,600 W50 A × 240 V12,000 W200 A × 240 V48,000 WCapacity (W) = amps × voltsSize the generator for your loads, not the rating
Capacity W = amps × volts

Worked example: fridge 725 + furnace blower 575 + sump 400 + LED 110 = 1,810 W running; + largest surge 1,725 W (blower) = 3,535 W minimum. Estimate only.

Preset watts and sources

LoadRunning WStarting WSource
Refrigerator (frost-free, 16 ft³)7252,175VCE BSE-301 nameplate 725 W; start ≈ 3× (BSE-301, MSU IS1921)
Freezer (½ hp motor)5752,300VT 442-067 Table 1/4 farm example: 575 W run, 2,300 W start
Furnace blower (⅓ hp motor)4002,000UF/IFAS AE033 Table 1, ⅓ hp motor: 400 W run, 2,000 W start (split-phase)
Furnace blower (½ hp motor)5752,300UF/IFAS AE033 Table 1, ½ hp motor: 575 W run, 2,300 W start
Well pump (½ hp)5752,300UF/IFAS AE033 Table 1, ½ hp: 575 / 2,300 W (VT 442-067 lists the same)
Well pump (1 hp)1,0004,000UF/IFAS AE033 Table 1, 1 hp: 1,000 / 4,000 W (VT 442-067 lists 1,075 / 4,300 W)
Sump pump (⅓ hp)4002,000UF/IFAS AE033 Table 1, ⅓ hp: 400 / 2,000 W
Sump pump (½ hp)5752,300UF/IFAS AE033 Table 1, ½ hp: 575 / 2,300 W
LED bulb (800 lm)1111DOE FEMP ENERGY STAR example 11 W per 800-lumen bulb; no motor, start = run
Microwave1,1001,100VCE BSE-301 range 750–1,100 W (upper end used); no start figure listed, start = run
Space heater (high)1,5001,500VCE BSE-301 range 750–1,500 W (high setting); resistive, start = run
Dehumidifier7852,355VCE BSE-301 nameplate 785 W; start ≈ 3× (BSE-301, MSU IS1921)
Electric water heater (240 V)4,5004,500VCE BSE-301 range 4,500–5,500 W (lower end used); 240 V resistive, start = run

Not included: window and central air conditioners and RV rooftop AC. No non-brand public source with both running and starting watts was found. Use the unit's nameplate and manual.

How it works

Total running watts = Σ (running watts × quantity). Surge = the largest single (starting watts − running watts). Minimum generator watts = total running + surge. This follows VT 442-067 Table 4, which adds the running load of everything else to one motor's start-up load, and Oklahoma State Extension's rule: add the running watts of everything needing power at the same time, then add the highest starting wattage. It assumes motors start one at a time. If two motors can start together, add both surges.

Motor presets come from the UF/IFAS AE033 single-phase motor table (running watts and starting watts by horsepower) and VT 442-067 Table 1, which assumes start-up is four times operating. Where only nameplate running watts are published (VCE BSE-301), starting watts use the cited rule that motors draw about three times running current to start (BSE-301; MSU Extension IS1921 says start current is typically three times operating). Resistive loads such as heaters, water heaters and lights use starting = running. Capacity of an electric service = amps × volts (NIST SI: W = V × A).

Optional elevation: derate fraction = (% per 1,000 ft ÷ 100) × max(0, elevation − start altitude) ÷ 1,000, and needed rating = minimum watts ÷ (1 − derate fraction), rounded up. The default 3.5% per 1,000 ft from sea level is the figure in the Westinghouse WGen20000 and Cummins Onan P4500iDF manuals. The Cummins Onan RV manual uses 3.5% with a 500 ft rating; Onan bulletin T-017 uses about 4% above 1,000 ft. Both fields are editable. Leave elevation blank for no derate.

More worked examples

  1. Larger home list: add a 1 hp well pump (1,000 / 4,000 W), a 4,500 W water heater and a 1,100 W microwave → 8,410 W running + 3,000 W (well pump surge) = 11,410 W.
  2. 30 A camper: microwave 1,100 + heater 1,500 + six LED bulbs 66 = 2,666 W, no motors → 2,666 W (74% of 3,600 W).
  3. 50 A RV: microwave 1,100 + two heaters 3,000 + fridge 725 + ten LED 110 = 4,935 W running + fridge surge 1,450 W = 6,385 W.
  4. Furnace blower only, ½ hp: 575 + (2,300 − 575) = 2,300 W.
  5. Well pump only, 1 hp: 1,000 + (4,000 − 1,000) = 4,000 W.
  6. Two sump pumps (⅓ hp, quantity 2): 800 W running + one surge of 1,600 W = 2,400 W, assuming they don't start at the same moment.

Generator size by situation

These are sections of this one page, not separate calculators. Each loads its example into the calculator above.

Essentials or whole-house loads

List what must run at the same time. VT 442-067 describes a part-load system that powers only critical loads, which needs a much smaller generator than powering everything at once.

Worked example (estimate): fridge 725 W + furnace blower (½ hp) 575 W + sump pump (⅓ hp) 400 W + ten 11 W LED bulbs 110 W = 1,810 W running. Largest start surge: blower 2,300 − 575 = 1,725 W. Minimum ≈ 3,535 W. Adding a 1 hp well pump (1,000 W), a 4,500 W water heater and a 1,100 W microwave gives 8,410 W running; the well pump's 4,000 − 1,000 = 3,000 W is then the largest surge, so the minimum is ≈ 11,410 W.

200 amp service: what it means for generator size

A 200 A service at 240 V can carry up to 200 × 240 = 48,000 W (W = V × A; VT 442-067 notes farm and home systems are usually 120/240 V single-phase). That is the panel's limit, not a typical load. Homes size the generator for the loads they choose to run, not for the service rating.

Worked example (estimate): the larger load list above (8,410 W running, 11,410 W minimum) is 8,410 ÷ 48,000 ≈ 17.5% of a 200 A service's 48,000 W.

30 amp camper

A 30 A camper outlet supplies 30 × 120 = 3,600 W, per KOA's RV electrical guide. A generator that matches that outlet needs about 3,600 running watts; a smaller load list needs less. RV rooftop air conditioners are not in the presets because no non-brand published running and starting figure was found. Use the unit's nameplate.

Worked example (estimate): a 1,100 W microwave + a 1,500 W space heater + six 11 W LED bulbs = 2,666 W running, no motor surge, so the minimum is ≈ 2,666 W, or about 74% of 3,600 W.

50 amp RV

A 50 A RV service is 120/240 V, so it supplies 50 × 240 = 12,000 W (KOA; Indiana's campground rules list a 50 A, 125/250 V receptacle). That is two 120 V legs of 50 A (6,000 W each).

Worked example (estimate): a 1,100 W microwave + two 1,500 W heaters + a 725 W fridge + ten LED bulbs = 4,935 W running. The fridge's start (2,175 − 725 = 1,450 W) is the largest surge, so the minimum is ≈ 6,385 W, with running load at about 41% of 12,000 W.

Generator for a furnace

A furnace still needs electricity for its blower motor and controls. Presets use the UF/IFAS motor table by horsepower. Read your furnace's rating plate for amps and the blower's horsepower.

Worked example (estimate): a ½ hp blower runs at 575 W and starts at 2,300 W, so alone it needs ≈ 2,300 W. A ⅓ hp blower (400 / 2,000 W) needs ≈ 2,000 W.

Generator for a well pump

Well pumps are motors with a large starting surge. UF/IFAS lists 4,000 W to start a 1 hp motor and 2,300 W for ½ hp. VT 442-067 gives 1,075 / 4,300 W for 1 hp, assuming start-up is four times operating, and notes start-up can be 2 to 12 times. Check the pump's nameplate voltage; many deep-well pumps are 240 V.

Worked example (estimate): a 1 hp pump: 1,000 running + (4,000 − 1,000) = ≈ 4,000 W. A ½ hp pump: ≈ 2,300 W.

Generator size at high elevation

Thinner air lowers engine power, so a generator delivers less than its rating at elevation. Needed rating = required watts ÷ (1 − derate fraction), where derate fraction = % per 1,000 ft × (elevation − start altitude) ÷ 1,000 ÷ 100. Derating varies by model; check your generator's manual.

Published sourceDerateStarts at
Westinghouse WGen20000 owner's manualabout 3.5% per 1,000 ftsea level
Cummins Onan P4500iDF operator manualabout 3.5% per 1,000 ftsea level
Cummins Onan RV operator manual A041D131 (Table 7)about 3.5% of rated power per 1,000 ftrated up to 500 ft
Onan Technical Bulletin T-017 (1974)about 4% per 1,000 ft (general rule)unnecessary below 1,000 ft

Worked example (estimate): the 3,535 W essentials list at 3,000 ft with 3.5% per 1,000 ft from sea level: derate = 3.5% × 3 = 10.5%; 3,535 ÷ 0.895 ≈ 3,950 W. With 4% above 1,000 ft: 8%; 3,535 ÷ 0.92 ≈ 3,843 W.

For reference, the USGS Elevation Point Query Service returns about 3,240 ft for a point in downtown Rapid City, South Dakota, and about 5,460 ft for a point in Lead, South Dakota (queried Oct 29, 2026). Use your own site's elevation.

How to measure

  1. Read each appliance's nameplate for watts, or volts × amps (use the watts and volts calculator).
  2. A plug-in watt meter shows real running watts for 120 V plug-in loads, including fridges and freezers as they cycle.
  3. For motors (well pump, sump, blower), read the horsepower and voltage on the motor plate and find starting watts or locked-rotor amps in the manual. Otherwise use the cited table above.
  4. For a hard-wired load, a licensed electrician can measure running current with a clamp-on ammeter (BSE-301 describes this method).
  5. List only the loads that must run at the same time.

Common mistakes

Assumptions

Frequently asked questions

What size generator do I need to run a house?

Add the running watts of everything you want on at once, then add the largest single starting surge. Fridge, ½ hp furnace blower, ⅓ hp sump and 10 LED bulbs come to about 3,535 W. Adding a 1 hp well pump, a 4,500 W water heater and a microwave raises it to about 11,410 W. These are estimates; your nameplates govern.

How do you calculate generator size?

Total running watts + the largest (starting − running) watts. This is the sequential-start method in VT 442-067 Table 4 and Oklahoma State Extension's rule: add the running watts, then the highest starting wattage.

What is the difference between running and starting watts?

Running watts are what a load draws once it is going. Motors draw much more for a moment to start. MSU Extension says start current is typically three times operating, and VT 442-067 says it can be 2 to 12 times.

How many watts is a 200 amp service?

200 A × 240 V = 48,000 W of capacity. That is the panel limit. Homes size a generator for the loads they choose to run, which is usually far less.

What size generator for a 30 amp camper?

A 30 A camper outlet supplies 30 × 120 = 3,600 W (KOA). To match it, a generator needs about 3,600 running watts. If your camper's actual loads are smaller, add them up instead.

What size generator for a 50 amp RV?

A 50 A RV service is 50 × 240 = 12,000 W (two 120 V legs of 50 A). Most RVs do not use all of it at once, so add up your real loads.

What size generator do I need to run a furnace?

For the blower motor alone: about 2,300 W for ½ hp (575 W running, 2,300 W starting) or 2,000 W for ⅓ hp, from the UF/IFAS motor table. Check the furnace rating plate.

What size generator do I need for a well pump?

About 4,000 W for a 1 hp pump (1,000 W running, 4,000 W starting, UF/IFAS) and about 2,300 W for ½ hp. VT 442-067 lists 4,300 W to start 1 hp. Check whether the pump is 120 V or 240 V.

How does elevation change generator size?

Engine power drops as air thins. The Westinghouse WGen20000 and Cummins Onan P4500iDF manuals say about 3.5% per 1,000 ft above sea level; Onan bulletin T-017 says about 4% per 1,000 ft above 1,000 ft. Needed rating = required watts ÷ (1 − derate fraction). Example: 3,535 W at 3,000 ft at 3.5% → about 3,950 W. Derating varies by model; check your generator's manual.

Can I plug a generator into a wall outlet to power the house?

No. CPSC warns never to power house wiring by plugging a generator into a wall outlet ("backfeeding"). OSHA says a generator should be connected only through a transfer switch installed by a qualified electrician.