Generator Size Calculator (Running and Starting Watts)
Direct answer: minimum generator watts ≈ total running watts of everything on at once + the largest single extra starting surge (starting − running watts). This is the method in Virginia Tech publication 442-067 (Table 4) and Oklahoma State Extension. Example: fridge 725 W + furnace blower 575 W + sump pump 400 W + 10 LED bulbs 110 W = 1,810 W running; the blower's 2,300 − 575 = 1,725 W surge is the largest, so the minimum is about 3,535 W. These are estimates. Your nameplates govern.
What to measure
Worked example: fridge 725 + furnace blower 575 + sump 400 + LED 110 = 1,810 W running; + largest surge 1,725 W (blower) = 3,535 W minimum. Estimate only.
Preset watts and sources
| Load | Running W | Starting W | Source |
|---|---|---|---|
| Refrigerator (frost-free, 16 ft³) | 725 | 2,175 | VCE BSE-301 nameplate 725 W; start ≈ 3× (BSE-301, MSU IS1921) |
| Freezer (½ hp motor) | 575 | 2,300 | VT 442-067 Table 1/4 farm example: 575 W run, 2,300 W start |
| Furnace blower (⅓ hp motor) | 400 | 2,000 | UF/IFAS AE033 Table 1, ⅓ hp motor: 400 W run, 2,000 W start (split-phase) |
| Furnace blower (½ hp motor) | 575 | 2,300 | UF/IFAS AE033 Table 1, ½ hp motor: 575 W run, 2,300 W start |
| Well pump (½ hp) | 575 | 2,300 | UF/IFAS AE033 Table 1, ½ hp: 575 / 2,300 W (VT 442-067 lists the same) |
| Well pump (1 hp) | 1,000 | 4,000 | UF/IFAS AE033 Table 1, 1 hp: 1,000 / 4,000 W (VT 442-067 lists 1,075 / 4,300 W) |
| Sump pump (⅓ hp) | 400 | 2,000 | UF/IFAS AE033 Table 1, ⅓ hp: 400 / 2,000 W |
| Sump pump (½ hp) | 575 | 2,300 | UF/IFAS AE033 Table 1, ½ hp: 575 / 2,300 W |
| LED bulb (800 lm) | 11 | 11 | DOE FEMP ENERGY STAR example 11 W per 800-lumen bulb; no motor, start = run |
| Microwave | 1,100 | 1,100 | VCE BSE-301 range 750–1,100 W (upper end used); no start figure listed, start = run |
| Space heater (high) | 1,500 | 1,500 | VCE BSE-301 range 750–1,500 W (high setting); resistive, start = run |
| Dehumidifier | 785 | 2,355 | VCE BSE-301 nameplate 785 W; start ≈ 3× (BSE-301, MSU IS1921) |
| Electric water heater (240 V) | 4,500 | 4,500 | VCE BSE-301 range 4,500–5,500 W (lower end used); 240 V resistive, start = run |
Not included: window and central air conditioners and RV rooftop AC. No non-brand public source with both running and starting watts was found. Use the unit's nameplate and manual.
How it works
Total running watts = Σ (running watts × quantity). Surge = the largest single (starting watts − running watts). Minimum generator watts = total running + surge. This follows VT 442-067 Table 4, which adds the running load of everything else to one motor's start-up load, and Oklahoma State Extension's rule: add the running watts of everything needing power at the same time, then add the highest starting wattage. It assumes motors start one at a time. If two motors can start together, add both surges.
Motor presets come from the UF/IFAS AE033 single-phase motor table (running watts and starting watts by horsepower) and VT 442-067 Table 1, which assumes start-up is four times operating. Where only nameplate running watts are published (VCE BSE-301), starting watts use the cited rule that motors draw about three times running current to start (BSE-301; MSU Extension IS1921 says start current is typically three times operating). Resistive loads such as heaters, water heaters and lights use starting = running. Capacity of an electric service = amps × volts (NIST SI: W = V × A).
Optional elevation: derate fraction = (% per 1,000 ft ÷ 100) × max(0, elevation − start altitude) ÷ 1,000, and needed rating = minimum watts ÷ (1 − derate fraction), rounded up. The default 3.5% per 1,000 ft from sea level is the figure in the Westinghouse WGen20000 and Cummins Onan P4500iDF manuals. The Cummins Onan RV manual uses 3.5% with a 500 ft rating; Onan bulletin T-017 uses about 4% above 1,000 ft. Both fields are editable. Leave elevation blank for no derate.
More worked examples
- Larger home list: add a 1 hp well pump (1,000 / 4,000 W), a 4,500 W water heater and a 1,100 W microwave → 8,410 W running + 3,000 W (well pump surge) = 11,410 W.
- 30 A camper: microwave 1,100 + heater 1,500 + six LED bulbs 66 = 2,666 W, no motors → 2,666 W (74% of 3,600 W).
- 50 A RV: microwave 1,100 + two heaters 3,000 + fridge 725 + ten LED 110 = 4,935 W running + fridge surge 1,450 W = 6,385 W.
- Furnace blower only, ½ hp: 575 + (2,300 − 575) = 2,300 W.
- Well pump only, 1 hp: 1,000 + (4,000 − 1,000) = 4,000 W.
- Two sump pumps (⅓ hp, quantity 2): 800 W running + one surge of 1,600 W = 2,400 W, assuming they don't start at the same moment.
Generator size by situation
These are sections of this one page, not separate calculators. Each loads its example into the calculator above.
Essentials or whole-house loads
List what must run at the same time. VT 442-067 describes a part-load system that powers only critical loads, which needs a much smaller generator than powering everything at once.
Worked example (estimate): fridge 725 W + furnace blower (½ hp) 575 W + sump pump (⅓ hp) 400 W + ten 11 W LED bulbs 110 W = 1,810 W running. Largest start surge: blower 2,300 − 575 = 1,725 W. Minimum ≈ 3,535 W. Adding a 1 hp well pump (1,000 W), a 4,500 W water heater and a 1,100 W microwave gives 8,410 W running; the well pump's 4,000 − 1,000 = 3,000 W is then the largest surge, so the minimum is ≈ 11,410 W.
200 amp service: what it means for generator size
A 200 A service at 240 V can carry up to 200 × 240 = 48,000 W (W = V × A; VT 442-067 notes farm and home systems are usually 120/240 V single-phase). That is the panel's limit, not a typical load. Homes size the generator for the loads they choose to run, not for the service rating.
Worked example (estimate): the larger load list above (8,410 W running, 11,410 W minimum) is 8,410 ÷ 48,000 ≈ 17.5% of a 200 A service's 48,000 W.
30 amp camper
A 30 A camper outlet supplies 30 × 120 = 3,600 W, per KOA's RV electrical guide. A generator that matches that outlet needs about 3,600 running watts; a smaller load list needs less. RV rooftop air conditioners are not in the presets because no non-brand published running and starting figure was found. Use the unit's nameplate.
Worked example (estimate): a 1,100 W microwave + a 1,500 W space heater + six 11 W LED bulbs = 2,666 W running, no motor surge, so the minimum is ≈ 2,666 W, or about 74% of 3,600 W.
50 amp RV
A 50 A RV service is 120/240 V, so it supplies 50 × 240 = 12,000 W (KOA; Indiana's campground rules list a 50 A, 125/250 V receptacle). That is two 120 V legs of 50 A (6,000 W each).
Worked example (estimate): a 1,100 W microwave + two 1,500 W heaters + a 725 W fridge + ten LED bulbs = 4,935 W running. The fridge's start (2,175 − 725 = 1,450 W) is the largest surge, so the minimum is ≈ 6,385 W, with running load at about 41% of 12,000 W.
Generator for a furnace
A furnace still needs electricity for its blower motor and controls. Presets use the UF/IFAS motor table by horsepower. Read your furnace's rating plate for amps and the blower's horsepower.
Worked example (estimate): a ½ hp blower runs at 575 W and starts at 2,300 W, so alone it needs ≈ 2,300 W. A ⅓ hp blower (400 / 2,000 W) needs ≈ 2,000 W.
Generator for a well pump
Well pumps are motors with a large starting surge. UF/IFAS lists 4,000 W to start a 1 hp motor and 2,300 W for ½ hp. VT 442-067 gives 1,075 / 4,300 W for 1 hp, assuming start-up is four times operating, and notes start-up can be 2 to 12 times. Check the pump's nameplate voltage; many deep-well pumps are 240 V.
Worked example (estimate): a 1 hp pump: 1,000 running + (4,000 − 1,000) = ≈ 4,000 W. A ½ hp pump: ≈ 2,300 W.
Generator size at high elevation
Thinner air lowers engine power, so a generator delivers less than its rating at elevation. Needed rating = required watts ÷ (1 − derate fraction), where derate fraction = % per 1,000 ft × (elevation − start altitude) ÷ 1,000 ÷ 100. Derating varies by model; check your generator's manual.
| Published source | Derate | Starts at |
|---|---|---|
| Westinghouse WGen20000 owner's manual | about 3.5% per 1,000 ft | sea level |
| Cummins Onan P4500iDF operator manual | about 3.5% per 1,000 ft | sea level |
| Cummins Onan RV operator manual A041D131 (Table 7) | about 3.5% of rated power per 1,000 ft | rated up to 500 ft |
| Onan Technical Bulletin T-017 (1974) | about 4% per 1,000 ft (general rule) | unnecessary below 1,000 ft |
Worked example (estimate): the 3,535 W essentials list at 3,000 ft with 3.5% per 1,000 ft from sea level: derate = 3.5% × 3 = 10.5%; 3,535 ÷ 0.895 ≈ 3,950 W. With 4% above 1,000 ft: 8%; 3,535 ÷ 0.92 ≈ 3,843 W.
For reference, the USGS Elevation Point Query Service returns about 3,240 ft for a point in downtown Rapid City, South Dakota, and about 5,460 ft for a point in Lead, South Dakota (queried Oct 29, 2026). Use your own site's elevation.
How to measure
- Read each appliance's nameplate for watts, or volts × amps (use the watts and volts calculator).
- A plug-in watt meter shows real running watts for 120 V plug-in loads, including fridges and freezers as they cycle.
- For motors (well pump, sump, blower), read the horsepower and voltage on the motor plate and find starting watts or locked-rotor amps in the manual. Otherwise use the cited table above.
- For a hard-wired load, a licensed electrician can measure running current with a clamp-on ammeter (BSE-301 describes this method).
- List only the loads that must run at the same time.
Common mistakes
- Adding every load's starting watts together. Motors rarely all start at once; the cited method adds one surge.
- Ignoring starting watts. A generator that runs a well pump may not start it.
- Sizing to the panel rating (48,000 W for 200 A) instead of the loads you need.
- Missing 240 V loads such as a deep-well pump or water heater. They need a 240 V generator output.
- Running a generator in a garage or near a window. CPSC and OSHA say CO can build up even with doors open.
- Backfeeding through a dryer or wall outlet instead of a transfer switch or interlock installed by a licensed electrician.
Assumptions
- Method: VT 442-067 Table 4 and Oklahoma State Extension (running total + largest start). The result is an arithmetic minimum. VT 442-067's worked examples add 20% for future expansion; this calculator does not add any margin.
- Starting watts vary a lot. VT 442-067 says start-up can be 2 to 12 times operating; its table uses 4×. UF/IFAS lists separate split-phase and capacitor-start figures (the higher is used for ⅓ hp). Use your motor's locked-rotor or starting figure if it's in the manual.
- Fridge and dehumidifier running watts are older VCE BSE-301 nameplate values; starting uses the cited ~3× rule. A modern unit may differ. A plug-in watt meter shows real running watts.
- Microwave starting is set equal to running because BSE-301 lists no starting figure. Edit it if your manual lists one.
- Omitted presets: window AC, central AC and RV rooftop AC (no non-brand source giving both running and starting watts). Enter nameplate values as a custom load.
- 200 A service = 200 × 240 = 48,000 W; 30 A camper = 30 × 120 = 3,600 W; 50 A RV = 50 × 240 = 12,000 W (KOA RV electrical guide; Indiana campground spec). These are capacity limits, not loads.
- Elevation is optional and blank by default (no derate). When set, the same derate % is applied to the whole minimum (running and starting). Default 3.5% per 1,000 ft from sea level (Westinghouse WGen20000, Cummins Onan P4500iDF manuals); the Cummins Onan RV manual rates to 500 ft; Onan T-017 says about 4% above 1,000 ft. Derating varies by model; check your generator's manual.
- Watts only. This page does not estimate fuel, run time or cost, and it does not size wiring, breakers or transfer equipment.
- Estimate only, not electrical code advice. See the safety box for CPSC, OSHA and Ready.gov guidance.
Frequently asked questions
What size generator do I need to run a house?
Add the running watts of everything you want on at once, then add the largest single starting surge. Fridge, ½ hp furnace blower, ⅓ hp sump and 10 LED bulbs come to about 3,535 W. Adding a 1 hp well pump, a 4,500 W water heater and a microwave raises it to about 11,410 W. These are estimates; your nameplates govern.
How do you calculate generator size?
Total running watts + the largest (starting − running) watts. This is the sequential-start method in VT 442-067 Table 4 and Oklahoma State Extension's rule: add the running watts, then the highest starting wattage.
What is the difference between running and starting watts?
Running watts are what a load draws once it is going. Motors draw much more for a moment to start. MSU Extension says start current is typically three times operating, and VT 442-067 says it can be 2 to 12 times.
How many watts is a 200 amp service?
200 A × 240 V = 48,000 W of capacity. That is the panel limit. Homes size a generator for the loads they choose to run, which is usually far less.
What size generator for a 30 amp camper?
A 30 A camper outlet supplies 30 × 120 = 3,600 W (KOA). To match it, a generator needs about 3,600 running watts. If your camper's actual loads are smaller, add them up instead.
What size generator for a 50 amp RV?
A 50 A RV service is 50 × 240 = 12,000 W (two 120 V legs of 50 A). Most RVs do not use all of it at once, so add up your real loads.
What size generator do I need to run a furnace?
For the blower motor alone: about 2,300 W for ½ hp (575 W running, 2,300 W starting) or 2,000 W for ⅓ hp, from the UF/IFAS motor table. Check the furnace rating plate.
What size generator do I need for a well pump?
About 4,000 W for a 1 hp pump (1,000 W running, 4,000 W starting, UF/IFAS) and about 2,300 W for ½ hp. VT 442-067 lists 4,300 W to start 1 hp. Check whether the pump is 120 V or 240 V.
How does elevation change generator size?
Engine power drops as air thins. The Westinghouse WGen20000 and Cummins Onan P4500iDF manuals say about 3.5% per 1,000 ft above sea level; Onan bulletin T-017 says about 4% per 1,000 ft above 1,000 ft. Needed rating = required watts ÷ (1 − derate fraction). Example: 3,535 W at 3,000 ft at 3.5% → about 3,950 W. Derating varies by model; check your generator's manual.
Can I plug a generator into a wall outlet to power the house?
No. CPSC warns never to power house wiring by plugging a generator into a wall outlet ("backfeeding"). OSHA says a generator should be connected only through a transfer switch installed by a qualified electrician.
Related calculators
- Power station runtime calculator – for how long a battery power station runs the same loads
- Watts, volts and amps calculator – to turn nameplate amps × volts into watts
- Voltage drop calculator – for cord or wire run voltage drop
- Space heater running cost calculator – for heater kWh on grid power
- Electrical & power calculators – Ah, watts, kW, kWh, voltage drop and home heating power tools
Sources
Formulas and reference values are from these sources. Page content last updated 2026-10-29.
- Virginia Tech / VCE 442-067: Standby electric generators for emergency farm use (Table 1 motor watts, start-up = 4× operating; Table 4 running load + one start-up load)
- University of Florida IFAS AE033: Auxiliary power units for greenhouse operations (Table 1 single-phase motor running and starting watts by hp)
- Oklahoma State University Extension (2020): add running watts of everything on at once, then the highest starting wattage
- Mississippi State University Extension IS1921: Selecting small portable electric generators (motor start current typically 3× operating)
- Virginia Cooperative Extension BSE-301: Estimating appliance and home electronic energy use (Wattage × hours ÷ 1,000 = daily kWh; portable heater 750-1,500 W)
- U.S. DOE FEMP Purchasing Energy-Efficient Light Bulbs Table 2: 800-lumen LED input power 5.9 to 10.5 W; Table 1 ENERGY STAR model example 11 W
- KOA: RV electrical 101 (30 A × 120 V = 3,600 W; 50 A × 240 V = 12,000 W)
- Indiana Department of Health: Campground electrical specifications (50 A, 125/250 V receptacle)
- NIST SP 330 (2019): The International System of Units (watt = J/s, volt = W/A)
- U.S. CPSC: Portable generator hazards (never indoors; CO alarms; never backfeed through a wall outlet)
- OSHA Fact Sheet 3286: Using portable generators safely (transfer switch by a qualified electrician; open doors may not prevent CO buildup)
- Ready.gov: Power outages (generators outdoors, 20 ft from windows, doors and attached garages; CO detectors on every level)
- Westinghouse WGen20000 owner's manual: maximum power decreases about 3.5% for each 1,000 ft above sea level (High Altitude Operation)
- Cummins Onan P4500iDF operator manual: maximum power decreases about 3.5% for each 1,000 ft above sea level
- Cummins Onan RV generator operator manual A041D131 §4.4.1: power decreases about 3.5% of rated power per 1,000 ft; Table 7 rated to 500 ft, 4,000 W → 3,720 W at 2,500 ft
- Onan Technical Bulletin T-017, Rating factors for electric generating sets (1974; archived copy): derate about 4% per 1,000 ft; unnecessary below 1,000 ft
- USGS Elevation Point Query Service (3DEP): point elevations, queried Oct 29, 2026